The Influence of External Parameters on Transformer Frequency Response Signature and Numerical Indices

2019

Closed access Metadata (CSL-JSON)
DOI 10.1109/eeeic.2019.8783609
Data confidence 85 high
How this score is calculated

It is built from checkable properties of the record itself: whether the article has a DOI, how many independent sources confirmed its data, whether the required fields are filled in, and how recent the latest confirmation is. Disagreement between sources and a missing identifier lower it. A value of 80 or above means the record was published without further checking; 60 to 79 means it is published at reduced confidence, with a manual check advisable. A record verified by an editor by hand is never pushed below 90 by a recalculation. This scores our data about the article, not the article itself.

Abstract

Frequency Response Analysis (FRA) is considered as a well-established technique to evaluate transformer winding and core structures. This evaluation would be reported in a wide frequency range spectrum. FRA is quite accurate technique; however, it is very sensitive to be affected via the external parameters. In this study, to analyze the external parameters influences on FRA spectrum, different topologies of external lumped parameters, namely series impedance, shunt impedance (ground resistance and capacitance to ground), and parallel to winding impedance are emulated, practically implemented and examined. In order to do that, four statistical indices such as Correlation Coefficient (CC), Euclidean distance, Root Mean Square Error (RMSE) and Absolute Sum of Logarithmic Error (ASLE) are calculated to explore the effect of external resistance and capacitance on Statistical Indicators (SIs). It is revealed that the most significant influence is caused by the impedance parallel to the winding. Moreover, individual analysis of statistical indices assists to identify a healthy region for each transformer unit.