Investigation of soils on the base of a reinforced concrete chimney

2023

Full text Open access: Hybrid Metadata (CSL-JSON)
DOI 10.1201/9781003299127-213
Data confidence 85 high
How this score is calculated

It is built from checkable properties of the record itself: whether the article has a DOI, how many independent sources confirmed its data, whether the required fields are filled in, and how recent the latest confirmation is. Disagreement between sources and a missing identifier lower it. A value of 80 or above means the record was published without further checking; 60 to 79 means it is published at reduced confidence, with a manual check advisable. A record verified by an editor by hand is never pushed below 90 by a recalculation. This scores our data about the article, not the article itself.

Abstract

The article presents the results of investigation of soils in the base and reasons for the collapse of a reinforced concrete chimney. Based on the materials of the conducted studies, it was concluded that the main reason for the collapse of the reinforced concrete shaft of the chimney of coke oven batteries no. 5 and no. 6 of arcelormittal temirtau jsc (formerly karaganda metallurgical plant) is a decrease in the strength characteristics of concrete due to many years of constant moisture, freezing and thawing in the autumn winter-spring periods of time, and indirectly due to the lack of proper control over the technical condition of building structures of all areas of reinforcement of the reinforced concrete chimney shaft and assessment of their strength characteristics. The design of the reinforcement instead of its original purpose contributed to the development of negative consequences and the safe operation of the facility.