Design method for checking tensile stresses under service loads in cracked prestressed concrete members with 2,400‐MPa strands

2019

Closed access Metadata (CSL-JSON)
DOI 10.1002/tal.1681
Data confidence 70 medium
How this score is calculated

It is built from checkable properties of the record itself: whether the article has a DOI, how many independent sources confirmed its data, whether the required fields are filled in, and how recent the latest confirmation is. Disagreement between sources and a missing identifier lower it. A value of 80 or above means the record was published without further checking; 60 to 79 means it is published at reduced confidence, with a manual check advisable. A record verified by an editor by hand is never pushed below 90 by a recalculation. This scores our data about the article, not the article itself.

Abstract

Summary The ACI 318‐14 building code requirements specify that the net tensile stresses of prestressing strands under service loads (Δfps) shall be limited to 250 MPa for proper crack control of prestressed concrete (PC) members which are classified as Class C. However, as high‐strength prestressing strands with a tensile strength of 2,400 MPa have recently been developed and applied to PC members, this requirement needs to be reviewed. In this study, experiments and analysis were carried out in order to investigate the Δfps of PC members with the recently developed 2400 MPa strands, and in the test, the strain distributions, flexural crack widths, and stress change in bonded prestressed reinforcement were measured in detail according to the applied loads. In addition, the minimum magnitudes of effective prestress to satisfy the stress limitation of the net tensile stress of prestressing strands specified in the current design code were estimated using a nonlinear flexural analysis model, and a simplified design equation was proposed for a simple calculation of the Δfps at the design stage.