Identification of design scheme parameters of electric network using WAMS data

2016

Closed access Metadata (CSL-JSON)
DOI 10.1109/pq.2016.7724124
Data confidence 70 medium
How this score is calculated

It is built from checkable properties of the record itself: whether the article has a DOI, how many independent sources confirmed its data, whether the required fields are filled in, and how recent the latest confirmation is. Disagreement between sources and a missing identifier lower it. A value of 80 or above means the record was published without further checking; 60 to 79 means it is published at reduced confidence, with a manual check advisable. A record verified by an editor by hand is never pushed below 90 by a recalculation. This scores our data about the article, not the article itself.

Abstract

Known algorithms for parameter identification of design scheme based on the observability of the need to observe the conditions for the entire complex scheme. This paper presents an algorithm for determining the longitudinal conductivity of (active and inductive) equivalent circuit of network using synchronized vector measurements. Applying power balance formula for a single node in a complex form, calculation of conductivities is made when presenting power lines in the form of U-shaped design scheme. The proposed algorithm is constructed of two equations for each branch adjacent to the considered node without the use of a series of calculations. The correctness of the proposed algorithm implemented for the transit circuit 500 kV of the National power grid.