Method for Determining the Single-Phase Ground Fault Current in a Three-Phase Electrical Network with an Isolated Neutral

2019

Closed access Metadata (CSL-JSON)
DOI 10.1109/iceee2019.2019.00012
Data confidence 70 medium
How this score is calculated

It is built from checkable properties of the record itself: whether the article has a DOI, how many independent sources confirmed its data, whether the required fields are filled in, and how recent the latest confirmation is. Disagreement between sources and a missing identifier lower it. A value of 80 or above means the record was published without further checking; 60 to 79 means it is published at reduced confidence, with a manual check advisable. A record verified by an editor by hand is never pushed below 90 by a recalculation. This scores our data about the article, not the article itself.

Abstract

A method for determining the single-phase ground fault current in an isolated neutral network with a voltage of up to 1000 V is proposed. This method is based on measuring the values of the line voltage, phase voltages when additional capacitive conductivity connected between one of network's phases and ground. The error analysis showed that the developed method provides satisfactory accuracy in determining the single-phase ground fault current, as well as the simplicity and safety of work in existing electrical installations with voltages up to 1000 V.