Frequency response technique to recognize turn-to-turn insulation deterioration in transformer winding

2016

Closed access Metadata (CSL-JSON)
DOI 10.1109/icpre.2016.7871182
Data confidence 70 medium
How this score is calculated

It is built from checkable properties of the record itself: whether the article has a DOI, how many independent sources confirmed its data, whether the required fields are filled in, and how recent the latest confirmation is. Disagreement between sources and a missing identifier lower it. A value of 80 or above means the record was published without further checking; 60 to 79 means it is published at reduced confidence, with a manual check advisable. A record verified by an editor by hand is never pushed below 90 by a recalculation. This scores our data about the article, not the article itself.

Abstract

One of the most important failure issues in transformers is the turn-to-turn short circuit fault. Turn-to-turn fault can be occurred due to the inter-turn paper insulation deterioration, or due to removing thin layer coated insulation between the winding turns. To date, there is no specific pre-determined method to find (or at least suspect) a deteriorated turn-to-turn insulation medium before catastrophic failure. Frequency Response Analysis (FRA) as a method introduced for transformer mechanical defect recognition, may be able to recognize the turn-to-turn fault potential and assist on this case. Hence, this study has concentrated practically on FRA capability to find turn-toturn insulation degradation as well as inter-turn aging rate. To this end, two different test objects are used and FRA signatures in various conditions are recorded. FRA results are provided and technically discussed.