Optimization of CCGT Start-Up Ramp Rate to Improve Voltage Quality in a 110/220 kV Power System Node

2026

Full text Open access: Gold Metadata (CSL-JSON)
DOI 10.3390/en19041028
Data confidence 70 medium
How this score is calculated

It is built from checkable properties of the record itself: whether the article has a DOI, how many independent sources confirmed its data, whether the required fields are filled in, and how recent the latest confirmation is. Disagreement between sources and a missing identifier lower it. A value of 80 or above means the record was published without further checking; 60 to 79 means it is published at reduced confidence, with a manual check advisable. A record verified by an editor by hand is never pushed below 90 by a recalculation. This scores our data about the article, not the article itself.

Abstract

With the active modernization of power facilities and the increasing deployment of maneuverable combined-cycle gas turbines (CCGTs), the selection of rational start-up strategies becomes increasingly important from the perspective of power quality. Excessive acceleration of power ramp-up may lead to undesirable voltage deviations, particularly in transmission networks with limited grid stiffness. This study investigates the impact of CCGT start-up ramp rate on voltage dynamics and power quality indicators at a 110/220 kV grid node. A detailed model of the Almaty power hub was developed in MATLAB/Simulink, taking into account the network structure, generating units, transformers, and aggregated loads. Three start-up scenarios were analyzed: an existing combined heat and power plant, a 504 MW combined-cycle gas turbine unit, and a 560 MW combined-cycle gas turbine unit with fuel afterburning. Voltage dynamics were evaluated using RMS-based indicators and a stabilization criterion incorporating a 5 s sliding time window and an 80% admissibility threshold. The simulation results reveal a nonlinear relationship between the start-up ramp rate and voltage quality. Increasing the ramp rate reduces the voltage stabilization time; however, beyond approximately 0.05 MW/s, further acceleration does not lead to additional improvement in power quality. The results indicate the existence of an optimal range of start-up ramp rates that provides a compromise between start-up speed and voltage quality requirements. The proposed approach can be used in the development of start-up algorithms for modern combined-cycle power plants connected to 110/220 kV transmission networks.