Evaluation of the Nurse-Saul method using maturity sensors for concrete strength control

Bulletin of the Karaganda University Physics Series, 2022

Full text Open access: Gold Metadata (CSL-JSON)
DOI 10.31489/2022ph1/66-74
Data confidence 70 medium
How this score is calculated

It is built from checkable properties of the record itself: whether the article has a DOI, how many independent sources confirmed its data, whether the required fields are filled in, and how recent the latest confirmation is. Disagreement between sources and a missing identifier lower it. A value of 80 or above means the record was published without further checking; 60 to 79 means it is published at reduced confidence, with a manual check advisable. A record verified by an editor by hand is never pushed below 90 by a recalculation. This scores our data about the article, not the article itself.

Abstract

The article presents the results of experimental studies on the strength of concrete grade B25 brand M350 by direct and indirect methods of control. To conduct tests, 17 cylindrical, 15 small, and 2 large cubic specimens were manufactured. 15 cylindrical specimens by 3 pieces were tested for compression in a hydraulic press on 1, 3, 7, 14, and 28 days of curing, and in the remaining two for 28 days the curing temperature was measured in order to obtain the strength-maturity relationship by the method of Nurse-Saul. The curing temperatures of the larger specimens were measured similarly, from which the concrete maturity and strength values on days 1, 3, 7, 14, and 28 were estimated. On the same days, compression tests were carried out on small specimens and by the shock pulse method on large specimens. As a result, the strength gain curves were obtained and calibration dependencies were plotted. The calibration dependencies showed a sufficiently close convergence of the results of the direct method of control (i.e., compression of small specimens) and the Nurse-Saul method of maturity, in contrast to those of the shock pulse method. The determination coefficients of these dependencies amounted to 0.9357 and 0.8965, respectively.