On-load tap-changer influence on frequency response analysis of transformer: A case study

2017

Closed access Metadata (CSL-JSON)
DOI 10.1109/demped.2017.8062394
Data confidence 70 medium
How this score is calculated

It is built from checkable properties of the record itself: whether the article has a DOI, how many independent sources confirmed its data, whether the required fields are filled in, and how recent the latest confirmation is. Disagreement between sources and a missing identifier lower it. A value of 80 or above means the record was published without further checking; 60 to 79 means it is published at reduced confidence, with a manual check advisable. A record verified by an editor by hand is never pushed below 90 by a recalculation. This scores our data about the article, not the article itself.

Abstract

Frequency Response Analysis (FRA) has been used as a comparative diagnosis method to explore mechanical defects in transformer. FRA is quite sensitive method and it can be influenced by different factors in transformer simply; however, this sensitivity will make it superior rather than other transformer winding deformation diagnosis techniques. This study has concentrated on tap-changer position influence on FRA signature. Practical study is performed on a 33 kV, 40 MVA three-phase core type transformer to examine on-load tap-changer (OLTC) position on frequency response spectrum in different frequency bands in Bode diagram. Oscillations in different frequency bands are discussed and their fluctuations are interpreted. Low-frequency band oscillations of FRA spectrum due to tap position changes are analyzed and discussed in detail. Distinguishing the tap-changer influence on FRA spectrum from winding deformation is quite crucial for FRA data interpretation.