Introduction of an Auxiliary Breaker into the Generator-Transformer Block for Energy Saving in Open Switchgear Circuits of Power Plants

2023

Full text Open access: Gold Metadata (CSL-JSON)
DOI 10.21122/1029-7448-2023-66-4-333-343
Data confidence 70 medium
How this score is calculated

It is built from checkable properties of the record itself: whether the article has a DOI, how many independent sources confirmed its data, whether the required fields are filled in, and how recent the latest confirmation is. Disagreement between sources and a missing identifier lower it. A value of 80 or above means the record was published without further checking; 60 to 79 means it is published at reduced confidence, with a manual check advisable. A record verified by an editor by hand is never pushed below 90 by a recalculation. This scores our data about the article, not the article itself.

Abstract

A need in finding of new ways of energy saving at open switchgears of power plants is substantiated. In order to increase energy saving efficiency, an auxiliary breaker is suggested to be inserted between a transformer of a block and its two high-voltage circuit breakers. The reasonability of such an insertion is proved on the basis of comparing of calculations resultsof under-discharge of electricity (UE) by the tabular-logical method (Yu. B. Guk) of the obtained schemes and of the traditional ones. For the calculations, the conditions that arose due to the change in the main circuit of a power plant are studied. Also, equations are given for calculation of a decrease in UE, damage due to it during reconstruction, and costs for the construction of a power plant (the costs are assumed to be the same in all options). Russian statistical data and the predicted failure rate λEV of a 750 kV SF6 circuit breaker are used. An option of the introduction of an SF6 circuit breaker with and without replacement of other circuit breakers with SF6 circuit breakers is considered. The results of calculations of UE, damage, and costs for the introduction suggested are tabulated, where changes in them due to the introduction of the circuit breaker are estimated for 18 ring circuits and 17 “3/2” and “4/3” circuits of 330–750 kV switchgears at condensation, nuclear, and hydroelectric power plants. It is demonstrated that the presence of a generator breaker in the blocks makes it possible to reduce these energy-saving efficiency indicators several times. A technique for determining the failure rate of a hypothetical circuit breaker, which, in the case of traditional replacement, is capable of producing the same effect as an SF6 circuit breaker inserted is proposed. An example of determining this frequency is given. Results of the calculated reduction of UE, damage and costs for the case of an air circuit breaker having been substituted to an SF6 circuit breaker are presented.