Experimental research of the developed method to determine the network insulation for ungrounded AC systems in laboratory conditions

2022

Closed access Metadata (CSL-JSON)
DOI 10.1109/icecet55527.2022.9873012
Data confidence 70 medium
How this score is calculated

It is built from checkable properties of the record itself: whether the article has a DOI, how many independent sources confirmed its data, whether the required fields are filled in, and how recent the latest confirmation is. Disagreement between sources and a missing identifier lower it. A value of 80 or above means the record was published without further checking; 60 to 79 means it is published at reduced confidence, with a manual check advisable. A record verified by an editor by hand is never pushed below 90 by a recalculation. This scores our data about the article, not the article itself.

Abstract

The article depicts the results of comparing the classical method and the developed method to determine insulation parameters in ungrounded AC systems. The developed method is based on measuring magnitudes of zero-sequence voltage, phase-to-earth voltage, and phase angles of the phase-to-earth voltage vector, and the zero-sequence voltage vector before and after connecting additional susceptance between the phase and earth. This article explains the sequence of measurements for the two methods in the laboratory conditions, where the results of the comparison confirm that the values of RMS errors and relative RMS errors of the developed and classical methods have good convergence. An experimental study of the developed method for determining insulation parameters demonstrates satisfactory accuracy and is a safer method compared to the classical method due to the absence of a single-phase earth fault.