Enhancing microgrid protection using dual-layer architecture and Battery Energy Storage Systems (BESS)

Energy Reports, 2026

Full text Open access: Gold Metadata (CSL-JSON)
DOI 10.1016/j.egyr.2026.109428
Data confidence 70 medium
How this score is calculated

It is built from checkable properties of the record itself: whether the article has a DOI, how many independent sources confirmed its data, whether the required fields are filled in, and how recent the latest confirmation is. Disagreement between sources and a missing identifier lower it. A value of 80 or above means the record was published without further checking; 60 to 79 means it is published at reduced confidence, with a manual check advisable. A record verified by an editor by hand is never pushed below 90 by a recalculation. This scores our data about the article, not the article itself.

Abstract

Conventional protection schemes face increasing difficulties as renewable energy sources and inverter-based resources (IBRs) contribute only limited fault current. This constraint frequently leads to slower fault detection, coordination issues, and reduced reliability, particularly during islanded operation. To address these challenges, this paper proposes two adaptive protection strategies: (1) virtual amplification of fault current through intelligent relay control and (2) active fault-current injection using Battery Energy Storage Systems (BESS). The strategies were implemented on the CIGRE benchmark network under three operating conditions, with OCR settings optimized using PSO, WCA, and TSA. Results indicate that TSA offers the best overall performance, achieving the lowest mean error and deviation (0.3–3.2) while maintaining moderate computation times of 9–12 s. It consistently outperformed WCA and PSO in accuracy, stability, and efficiency. Furthermore, total tripping times decreased substantially, most notably in islanded mode, where they fell from 49.35 s (SOCR) to 29.12 s and 32.56 s. To further evaluate the robustness of the proposed methods, an additional islanded high-impedance fault scenario with R f = 10 Ω is investigated, revealing that fault resistance has a limited impact on current levels due to the voltage-dependent behavior of inverter-based resources. These outcomes demonstrate the effectiveness of the proposed strategies in enhancing relay performance, reducing operating times, and improving the resilience of distribution-system protection.