Negative Impact Mitigation on the Power Supply System of a Fans Group with Frequency-Variable Drive

2022

Full text Open access: Gold Metadata (CSL-JSON)
DOI 10.3390/en15238858
Data confidence 70 medium
How this score is calculated

It is built from checkable properties of the record itself: whether the article has a DOI, how many independent sources confirmed its data, whether the required fields are filled in, and how recent the latest confirmation is. Disagreement between sources and a missing identifier lower it. A value of 80 or above means the record was published without further checking; 60 to 79 means it is published at reduced confidence, with a manual check advisable. A record verified by an editor by hand is never pushed below 90 by a recalculation. This scores our data about the article, not the article itself.

Abstract

The technological installations’ characteristics are possible to improve by equipping fans with a frequency-controlled electric drive. However, it can lead to an electromagnetic compatibility problem in the electrical supply system. This problem becomes worse if a large number of fans are included in the technological installation and the electric drives are powered from a substation connected to a limited power source. As an example, in this article we investigate the power supply system of a gas cooling unit with variable-frequency electric drives for fans. The electric drives’ operating mode dependences characterizing the non-sinusoidal voltages and currents of the power source are obtained with the help of simulation modeling in the MATLAB environment with the Simulink expansion package. The typical substation circuit usage for the power supply of a group of fans with a frequency-controlled drive does not meet the requirements of IEEE Standard 519-2014. We can solve the problem of electromagnetic compatibility by changing the substation topology and organizing DC busbars and replacing frequency converters with inverters. We proposed forming DC busbars using 12-pulse rectifiers powered by transformers with two secondary windings with different connection schemes. The simulation results confirmed that the proposed substation topology provides the voltage and current harmonics level on the substation power busbars in accordance with the IEEE Standard 519-2014 requirements over the entire frequency range of the fans’ motor control.